ELECTRIC POWER DIVISIONTransformer Wireless Load Monitoring System (DTMS),
Fault Current Path Monitoring System (FPI), POWER CT

FPI

Feature

  • It is designed monitoring of outdoor on MV line
  • The LED indicates fault type as Phase to phase and Earth fault
  • Set up parameter by Web or Dip Switch
  • Self reset after recovery or manual reset
  • Set fault range 10A to 100A
  • Operating by built-in battery

Characteristics

Frequency50Hz and 60Hz
Fault TypePhase to Phase fault/Phase to earth
Load>2A
Phase fault100 to 800A
Earth fault20 to 160A
Fault acknowledge Time delay40ms
Confirmation time delay70s
Inrush time delay3s
ResetAuto(upon current return 2A)
Manual via front panel/External contact(web)
IndicationLED
BatteryLithium
Display4-digit LCD/Fault:RED
Phase CTSpilit CTs